Compare Products

Generac Protector 100kW
Generac Protector 100kW

Specs

General Information

Manufacturer
Generac
Generac
Model
Protector 100kW
Protector 100kW
Model Code
RG10090
RG10090
Color
Bisque
Bisque

Engine

Engine Make
Generac
Generac
Fuel Type
Natural gas, Propane vapor
Natural gas, Propane vapor
Oil Capacity

Crankcase - 10.5 qt. (9.9 l)

Oil pump type - Gear

Oil filter type - Full Flow Spin-On Cartridge

Crankcase - 10.5 qt. (9.9 l)

Oil pump type - Gear

Oil filter type - Full Flow Spin-On Cartridge

Bore x Stroke
4.5 x 4.25 in. (114.3 x 107.95 mm)
4.5 x 4.25 in. (114.3 x 107.95 mm)
Compression Ratio
9.9:1
9.9:1
Alternator

Type - Synchronous

Rotor insulation class - H

Stator insulation class - H

Telephone Interference Factor (TIF) - < 50

Output leads 1-phase - 4 wire

Output leads 3-phase - 12 wire

Bearings - Sealed ball

Coupling - Flexible disc

Excitation system - Brushless

Total Harmonic Distortion - < 5%

Type - Synchronous

Rotor insulation class - H

Stator insulation class - H

Telephone Interference Factor (TIF) - < 50

Output leads 1-phase - 4 wire

Output leads 3-phase - 12 wire

Bearings - Sealed ball

Coupling - Flexible disc

Excitation system - Brushless

Total Harmonic Distortion - < 5%

Displacement
540 cc (8.86 l)
540 cc (8.86 l)
Fuel Consumption

Carburetor - Down Draft

Secondary Fuel Regulator

Fuel Shut Off Solenoid

LP / NG Fuel Pressure - 11 - 14 in Water Column

25% of rated load (Natural Gas) - 406 cu. ft. / hr. (11.5 m³ / hr.)

25% of rated load (Propane) - 20 cu. ft. / hr. (0.56 m³ / hr.)

50% of rated load (Natural Gas) - 655 cu. ft. / hr. (18.5 m³ / hr.)

50% of rated load (Propane) - 294 cu. ft. / hr. (8.3 m³ / hr.)

75% of rated load (Natural Gas) - 896 cu. ft. / hr. (25.4 m³ / hr.)

75% of rated load (Propane) - 425 cu. ft. / hr. (12.0 m³ / hr.)

100% of rated load (Natural Gas) - 1,128 cu. ft. / hr. (31.9 m³ / hr.)

100% of rated load (Propane) - 528 cu. ft. / hr. (15.0 m³ / hr.)

Carburetor - Down Draft

Secondary Fuel Regulator

Fuel Shut Off Solenoid

LP / NG Fuel Pressure - 11 - 14 in Water Column

25% of rated load (Natural Gas) - 406 cu. ft. / hr. (11.5 m³ / hr.)

25% of rated load (Propane) - 20 cu. ft. / hr. (0.56 m³ / hr.)

50% of rated load (Natural Gas) - 655 cu. ft. / hr. (18.5 m³ / hr.)

50% of rated load (Propane) - 294 cu. ft. / hr. (8.3 m³ / hr.)

75% of rated load (Natural Gas) - 896 cu. ft. / hr. (25.4 m³ / hr.)

75% of rated load (Propane) - 425 cu. ft. / hr. (12.0 m³ / hr.)

100% of rated load (Natural Gas) - 1,128 cu. ft. / hr. (31.9 m³ / hr.)

100% of rated load (Propane) - 528 cu. ft. / hr. (15.0 m³ / hr.)

Battery

Charger Alternator - 40 A

Static charger - 2.5 A

Recommended - Group 31, 925 CCA

System voltage - 12 V

Charger Alternator - 40 A

Static charger - 2.5 A

Recommended - Group 31, 925 CCA

System voltage - 12 V

Cooling

Pressurized Closed

System coolant capacity - 5.5 gal. (20.8l)

Water pump - Belt driven

Fan speed - 2,330 rpm

Fan diameter - 22 in. (55.9 cm)

Fan mode - Pusher

Pressurized Closed

System coolant capacity - 5.5 gal. (20.8l)

Water pump - Belt driven

Fan speed - 2,330 rpm

Fan diameter - 22 in. (55.9 cm)

Fan mode - Pusher

Engine Model
8 cylinder
8 cylinder
Engine Type
V
V

Measurements

Weight
Shipping - 3,024 lb. (1,371 kg)
Shipping - 3,024 lb. (1,371 kg)
Height
Overall - 69.3 in. (1,761 mm)
Overall - 69.3 in. (1,761 mm)
Width
Overall - 39.5 in. (1,003 mm)
Overall - 39.5 in. (1,003 mm)
Length
Overall - 110.6 in. (1,810 mm)
Overall - 110.6 in. (1,810 mm)

Operational

AC Frequency
60 Hz
60 Hz
Noise Level
Sound output in 71 dB(A) @ 23 ft. (7 m) with generator in normal operation
Sound output in 71 dB(A) @ 23 ft. (7 m) with generator in normal operation
Maximum Temperature
Ambient - 122 °F (50 °C)
Ambient - 122 °F (50 °C)
DC Output

120 / 240 V, 1Ø, 1.0 pf (LPG / NG) - 96 kW, 400 A, 400 CB

120 / 208 V, 3Ø, 0.8 pf (LPG) - 100 kW, 347 A, 400 CB

120 / 208 V, 3Ø, 0.8 pf (NG) - 96 kW, 333 A, 400 CB

120 / 240 V, 3Ø, 0.8 pf (LPG) - 100 kW, 300 A, 350 CB

120 / 240 V, 3Ø, 0.8 pf (NG) - 96 kW, 288 A, 350 CB

277 / 480 V, 3Ø, 0.8 pf (LPG) - 100 kW, 150 A, 175 CB

277 / 480 V, 3Ø, 0.8 pf (NG) - 96 kW, 144 A, 175 CB

120 / 240 V, 1Ø, 1.0 pf (LPG / NG) - 96 kW, 400 A, 400 CB

120 / 208 V, 3Ø, 0.8 pf (LPG) - 100 kW, 347 A, 400 CB

120 / 208 V, 3Ø, 0.8 pf (NG) - 96 kW, 333 A, 400 CB

120 / 240 V, 3Ø, 0.8 pf (LPG) - 100 kW, 300 A, 350 CB

120 / 240 V, 3Ø, 0.8 pf (NG) - 96 kW, 288 A, 350 CB

277 / 480 V, 3Ø, 0.8 pf (LPG) - 100 kW, 150 A, 175 CB

277 / 480 V, 3Ø, 0.8 pf (NG) - 96 kW, 144 A, 175 CB

DC Voltage

Regulation type - Full Digital

Regulation sensing - All

Regulation - Designed for Sensitive Electronics

Regulation type - Full Digital

Regulation sensing - All

Regulation - Designed for Sensitive Electronics

Instrumentation

Two-Line LCD Multilingual Digital Evolution™ Controller (English / Spanish / French / Portuguese)

Two-Line Plain Text LCD Display - Simple user interface for ease of operation.

Two-Line LCD Multilingual Digital Evolution™ Controller (English / Spanish / French / Portuguese)

Two-Line Plain Text LCD Display - Simple user interface for ease of operation.

Other

Warranty
5 year limited
5 year limited

Features

Enclosure

  • ALUMINUM WEATHER PROTECTIVE ENCLOSURE: Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
  • ENCLOSED CRITICAL GRADE MUFFLER: Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
  • SMALL, COMPACT, ATTRACTIVE: Makes for an easy, eye appealing installation.
  • SAE WEATHER PROTECTIVE ENCLOSURE: Sound attenuated enclosure ensures quiet operation.

Features

  • 5-Year Limited Warranty - Consistent with the Protector Series lineup, 5-year limited warranty is standard.
  • True Power™ Technology delivers best-in-class power quality with less than 5 percent total harmonic distortion for clean, smooth operation of sensitive electronics and appliances.
  • Tough, Durable All-Aluminum Enclosures: Our RhinoCoat™ powder-coated finish helps make corrosion-resistant aluminum perfect for all weather conditions.
  • 24/7/365 Customer Support Team standing by all day, every day from our headquarters in Wisconsin to answer any questions you might have.
  • Smart, User-Friendly Controls. Generac’s Evolution™ Controller features a multilingual LCD display that allows users to monitor battery status and track maintenance intervals to ensure your generator is always in top operating condition.
  • Quiet-Test™ Self-Test Mode runs at a lower RPM for a five- or twelve-minute test, making generators significantly quieter than other brands while consuming less fuel.
  • Mobile Link™ Remote Monitoring - Allows you to monitor the status of your generator from anywhere in the world using a smartphone, tablet, or PC. Easily access information, such as the current operating status and maintenance alerts. Connect your account to your authorized service dealer for fast, friendly, and proactive service. With Mobile Link, you are taken care of before the next power outage.
  • Generac generators and engines are engineered and built in the USA*. *Assembled in the USA using domestic and foreign parts
  • Generac Designed & Built Engine - Purpose-built exclusively for generator use. Engine originally designed and built for Generac Industrial applications.
  • INNOVATIVE DESIGN & PROTOTYPE TESTING: are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
  • TEST CRITERIA: Prototype tested. Nema mg1-22 evaluation. System torsional tested. Motor starting ability.
  • MOBILE LINK® CONNECTIVITY: Free with select Protector Series standby generator sets, Mobile Link Wi-Fi allows users to monitor the generator set status from anywhere in the world using a smartphone, tablet, or PC. Easily access information such as the current operating status and maintenance alerts. Users can connect an account to an authorized service dealer for fast, friendly, and proactive service. With Mobile Link, users are taken care of before the next power outage.
  • SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION: This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine.
  • SINGLE SOURCE SERVICE RESPONSE: from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
  • GENERAC TRANSFER SWITCHES: Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is the GENERAC product line is offered with its own transfer systems and controls for total system compatibility.
  • Intake Air System - Naturally Aspirated
  • Lifter Type - Hydraulic Roller
  • Carburetor - Down Draft
  • Secondary Fuel Regulator
  • Fuel Shut Off Solenoid
  • LP / NG Fuel Pressure - 11 - 14 in Water Column
  • Governor Type - Electronic
  • Governor Frequency Regulation - Isochronous
  • Governor Steady State Regulation - Designed for Sensitive Electronics
  • Air Flow (Fan Air Flow Across Radiator) - Open Set - 6,589 scfm (186 m³ / min)
  • Flow at Rated Power - 230 scfm (6.5 m³ / min)
  • Exhaust Flow at Rated Output - 771 scfm (21.8 m³ /min)
  • Exhaust Temperature (Rated Output) - 1,350 °F (732 °C)
  • Rated Engine Speed - 1,800 rpm
  • Temperature deration on NG & LP - 3.3% per 10°F above 77°F
  • Altitude deration on NG & LP - 3% for every 1,000 ft. above 600 ft.
  • Auto mode switch - Automatic Start on Utility failure. 7 day exerciser.
  • Off mode switch - Stops unit. Power is removed. Control and charger still operate.
  • Manual mode switch - Start with starter control, unit stays on. If utility fails, transfer to load takes place.
  • Programmable Start Delay Between 10-30 Seconds - 10 sec standard
  • Engine Start Sequence - Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration)
  • Engine Warm-up - 5 sec
  • Engine Cool-Down - 1 min
  • Starter Lock-Out - Starter cannot re-engage until 5 sec after engine has stopped.
  • Overspeed Shutdown - Standard, 72 Hz
  • Smart Battery Charger, Automatic Voltage Regulation With Over and Under Voltage Protection, Automatic Low Oil Pressure Shutdown, High Temperature Shutdown, Overcrank Protection, Safety Fused, Failure to Transfer Protection, Low Battery Protection, 50 Event Run Log, Future Set Capable Exerciser, Incorrect Wiring Protection, Internal Fault Protection, Common External Fault Capability, Governor Failure Protection

Generator

  • Revolving field heavy duty generator
  • Directly connected to the engine
  • Operating temperature rise 135° C above 25° C ambient
  • Class H insulation is NEMA rated
  • All models fully prototyped tested

Enclosure

  • ALUMINUM WEATHER PROTECTIVE ENCLOSURE: Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
  • ENCLOSED CRITICAL GRADE MUFFLER: Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
  • SMALL, COMPACT, ATTRACTIVE: Makes for an easy, eye appealing installation.
  • SAE WEATHER PROTECTIVE ENCLOSURE: Sound attenuated enclosure ensures quiet operation.

Features

  • 5-Year Limited Warranty - Consistent with the Protector Series lineup, 5-year limited warranty is standard.
  • True Power™ Technology delivers best-in-class power quality with less than 5 percent total harmonic distortion for clean, smooth operation of sensitive electronics and appliances.
  • Tough, Durable All-Aluminum Enclosures: Our RhinoCoat™ powder-coated finish helps make corrosion-resistant aluminum perfect for all weather conditions.
  • 24/7/365 Customer Support Team standing by all day, every day from our headquarters in Wisconsin to answer any questions you might have.
  • Smart, User-Friendly Controls. Generac’s Evolution™ Controller features a multilingual LCD display that allows users to monitor battery status and track maintenance intervals to ensure your generator is always in top operating condition.
  • Quiet-Test™ Self-Test Mode runs at a lower RPM for a five- or twelve-minute test, making generators significantly quieter than other brands while consuming less fuel.
  • Mobile Link™ Remote Monitoring - Allows you to monitor the status of your generator from anywhere in the world using a smartphone, tablet, or PC. Easily access information, such as the current operating status and maintenance alerts. Connect your account to your authorized service dealer for fast, friendly, and proactive service. With Mobile Link, you are taken care of before the next power outage.
  • Generac generators and engines are engineered and built in the USA*. *Assembled in the USA using domestic and foreign parts
  • Generac Designed & Built Engine - Purpose-built exclusively for generator use. Engine originally designed and built for Generac Industrial applications.
  • INNOVATIVE DESIGN & PROTOTYPE TESTING: are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.
  • TEST CRITERIA: Prototype tested. Nema mg1-22 evaluation. System torsional tested. Motor starting ability.
  • MOBILE LINK® CONNECTIVITY: Free with select Protector Series standby generator sets, Mobile Link Wi-Fi allows users to monitor the generator set status from anywhere in the world using a smartphone, tablet, or PC. Easily access information such as the current operating status and maintenance alerts. Users can connect an account to an authorized service dealer for fast, friendly, and proactive service. With Mobile Link, users are taken care of before the next power outage.
  • SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION: This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine.
  • SINGLE SOURCE SERVICE RESPONSE: from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
  • GENERAC TRANSFER SWITCHES: Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is the GENERAC product line is offered with its own transfer systems and controls for total system compatibility.
  • Intake Air System - Naturally Aspirated
  • Lifter Type - Hydraulic Roller
  • Carburetor - Down Draft
  • Secondary Fuel Regulator
  • Fuel Shut Off Solenoid
  • LP / NG Fuel Pressure - 11 - 14 in Water Column
  • Governor Type - Electronic
  • Governor Frequency Regulation - Isochronous
  • Governor Steady State Regulation - Designed for Sensitive Electronics
  • Air Flow (Fan Air Flow Across Radiator) - Open Set - 6,589 scfm (186 m³ / min)
  • Flow at Rated Power - 230 scfm (6.5 m³ / min)
  • Exhaust Flow at Rated Output - 771 scfm (21.8 m³ /min)
  • Exhaust Temperature (Rated Output) - 1,350 °F (732 °C)
  • Rated Engine Speed - 1,800 rpm
  • Temperature deration on NG & LP - 3.3% per 10°F above 77°F
  • Altitude deration on NG & LP - 3% for every 1,000 ft. above 600 ft.
  • Auto mode switch - Automatic Start on Utility failure. 7 day exerciser.
  • Off mode switch - Stops unit. Power is removed. Control and charger still operate.
  • Manual mode switch - Start with starter control, unit stays on. If utility fails, transfer to load takes place.
  • Programmable Start Delay Between 10-30 Seconds - 10 sec standard
  • Engine Start Sequence - Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration)
  • Engine Warm-up - 5 sec
  • Engine Cool-Down - 1 min
  • Starter Lock-Out - Starter cannot re-engage until 5 sec after engine has stopped.
  • Overspeed Shutdown - Standard, 72 Hz
  • Smart Battery Charger, Automatic Voltage Regulation With Over and Under Voltage Protection, Automatic Low Oil Pressure Shutdown, High Temperature Shutdown, Overcrank Protection, Safety Fused, Failure to Transfer Protection, Low Battery Protection, 50 Event Run Log, Future Set Capable Exerciser, Incorrect Wiring Protection, Internal Fault Protection, Common External Fault Capability, Governor Failure Protection

Generator

  • Revolving field heavy duty generator
  • Directly connected to the engine
  • Operating temperature rise 135° C above 25° C ambient
  • Class H insulation is NEMA rated
  • All models fully prototyped tested